My status
Manufacturer
Product search
April  30 , 2024  Tuesday
Home> display record >> regulator >> XTMA(H)-1000A-Dsmart digital display regulator
  • Product number:MC-000044005524
  • Product name:smart digital display regulator
  • Product Type:XTMA(H)-1000A-D
  • Product nameplate:SAIC
  • Project Category:display record >> regulator >>
  • Manufacturer:Shanghai Automation Instrumentation Co., Ltd.
  • Sales unit: Shanghai Automation Instrumentation Marketing Center
  • Information download:Click to enter the download page  
  • Introduction
  • Specifications
Use advanced SMT surface mount technology. Use advanced switch power, light weight, full input, accuracy is ±0.5FS±1dig. resolution is 14dit. Linear input range can be free moved. Error amend. Mangy regulation output, PID self-adjusting function. Manual/automatic switch. Two groups of relay output, for alarming or regulating. Process volume output. Supply 24V power, two-row four-bit display. Data stored in E2PROM
Input type
Thermocouple
B:0~1800℃  S:0~1600℃
K:0~1300℃  E:0~800℃
T:0~300℃  J:0~800℃
WU-Re3-25   0~2000℃
Thermal resistance
Pt100(L):-100.0~300℃
Pt100(H):-200~600℃
Cu50    :0.0~150.0℃
Linear input
mV input:0~10mv.DC;0~50mV.DC  0~100mv.DC
voltage input:0~5V DC;    1~5V.DC
current input:0~10mA.DC:4~20mA DC
Radiation sensing device  WFT-202(F1 Quartz glass)400~1200℃
WFT-202(F2,K9 glass)700~2000℃
Output type
Control mode
0:current  0~10mA.DC(max load resistance 1.5kΩ)
1:current  4-20mA.DC((max load resistance 800Ω)
2:relay   contact capacity  3A/250VAC resistive load
SSR solid relay   capacity  1A/250VAC resistive load
Pulse voltage   24VDC(max current 30mA)
Control parameters
Proportional band (Pb) 0~400.0%
Integration time (Ti) 0-3600s
Differential time (Td) 0~1800s
Control insensitive zone (Hy) 0~9999
Control circle (t) 1~120s
Alarm
1 upper limit alarm
2.lower limit alarm(two-bit control)
3.upper, lower limit alarm(three-bit control)
4. upper, lower limit alarm
5. upper, lower limit alarm
Insensitive area: 0~9999 adjustable
Contact capacity, 2A、250V AC, non inductive load
Process volume output   0~10mA DC、4~20mA DC、0~5V.DC   1~5V DC
Supply voltage
Power of transformer: 220V 4-10%50Hz~60Hz
Switching power: 85V~264VAC  50Hz~60Hz
Power of transmitter: 24V、30mADC