Repeatability error: ±3 digits
Indication error: less than 10% of full range
Protection of even off: When the thermocouple circuit, the deviation of the table should be positive deviation pointer beyond the end of sub-degree line.
Working environment :temperature O~50℃, relative humidity: less than 85%, Vibration-free, non-corrosive gases occasions
Power supply: 220V±10%50Hz
Weight : <4.2kg
Outside resistance: 5Ω
Output : Relay contact 220V 3A (no sense of load)
Alarm Action: less than O.5% of Deviation Table
Sensitivity: <0.5%
2 PID
Control accuracy : 0.5%
Cycle : 40±10s
Regulation parameters : P:10-300%×0.9×(360×10V/Full power range ×K)×100%
I:0.25~7 points D:0~1.5 points
Output : Relay contact 220V 3A (no sense of load)
3 PID
Sensitivity: 0.3%
Regulation parameters : P:0.5%~(Ty×2250/Full power range×K)×100N T:0.5~14 points
Output : Relay contact 220V 3A (no sense of the load) 220V 3A (felt load), instrument panel with manual switch and manual operation button continuous PID
Sensitivity:0.1%
Regulation parameters : P:10~300% I:0.25~7 points D:0~1.5 points
Output: O ~ 10mA.DC (load 1KΩ) instrument panel equipped with hand-automatic and manual operation switch button, a deviation of equal to zero when the manual switch D automatically without disturbance.
Mode specifications
Functions |
Mode specifications |
Terminal diagram No. |
Bit-type + Alarm |
TA-011、012 |
51—0l~02 |
Time ratio |
TA-031、032 |
51—03~04 |
2 PID |
TA-041、042 |
51—03~04 |
3 PI |
TA-051,052、053、054、055、056、057 |
51—05~06,52—01 |
Continue PID |
TA-091、092、093、094、095、096、097 |
52—02~04 |
Note: This series of instruments are equipped with actuators:
Contactors, solenoid valves, ZAP (ZAJ) straight stroke motor + ZM film valves, SCR voltage regulators, DF-1 servo amplifier + straight stroke motor + ZM film valves, electrical converter + ZM pneumatic membrane valves