Home> unit meter >> barrier >> KAG(kFA)-5300Isolated Safety Barrier
  • Product number:MC-000467001370
  • Product name:Isolated Safety Barrier
  • Product Type:KAG(kFA)-5300
  • Product nameplate:SAIC
  • Project Category:unit meter >> barrier >>
  • Manufacturer:Shanghai Automation Instrumentation Co., Ltd.
  • Sales unit: Shanghai Automation Instrumentation Marketing Center
  • Information download:Click to enter the download page  
  • Introduction
  • Specifications
KAG-5□□□ isolated safety barrier is a type of cassette-series instrument. In normal state, safety barrier does not affect the normal operation of the system. When it is fault, the safety barrier will limit voltage and current and restrict electric energy within limits to ensure safety. It is widely used in petroleum, chemical industry, light industry and other inflammable and explosive places. It has the following characteristics:
Detected terminal barrier is used with two-wire transmitter and supply power for it. It can restrict dangerous energy enter into dangerous place. Isolated safety barrier can convert 4~20mADC signal from transmitter to isolated 4~20mADC signal output.
To compare with zener safety barrier, isolated safety barrier can isolate signal. Cassette-type can be installed on DIN rails to save the control cabinet space.
Model mark
K
A
G
Cassette-type
instrument
Safety barrier
Isolated type
5)
transmitter+
capacity
isolated
 
1) detected
terminal
2) Single operated terminal
 
0)
Normal-type
1)
input/output、input/power
isolated
Power supply:24±10%VDC
Input signal:4~20mADC
Output signal:4~20mADC
Output impedance:Detected terminal ≤750Ω; operated terminal ≤750Ω
Limit voltage:UK:<28V
Limit current:IK:<93mA
Explosion-proof grade:Ex(ia)ⅡC
Ambient temperature:5~40℃
RH:5%~85%
Working frequency:10~55Hz,amplitude: 0.075mm
External magnetic field:≤400A/m
Without corrosive media which impact nickel, chrome plating, non-ferrous metals and alloys in ambient.
,