Home> unit meter >> barrier >> KAG-1□01HIsolated Safety Barrier
  • Product number:MC-000467001366
  • Product name:Isolated Safety Barrier
  • Product Type:KAG-1□01H
  • Product nameplate:SAIC
  • Project Category:unit meter >> barrier >>
  • Manufacturer:Shanghai Automation Instrumentation Co., Ltd.
  • Sales unit: Shanghai Automation Instrumentation Marketing Center
  • Information download:Click to enter the download page  
  • Introduction
  • Specifications
KAG-1口01/H isolated safety barrier is a type of cassette-series instrument which support HART communication. When it is fault, the safety barrier will limit voltage and current and restrict electric energy within limits to ensure safety. It is widely used in petroleum, chemical industry, light industry and other inflammable and explosive places. It has the following characteristics:
Detected terminal barrier is used with two-wire transmitter and supply power for it. It can restrict dangerous energy enter into dangerous place. Isolated safety barrier can convert 4~20mADC signal from transmitter to isolated 4~20mADC signal output and support HART digital signal dual transmission. To compare with zener safety barrier, isolated safety barrier can isolate signal. Cassette-type can be installed on DIN rails to save the control cabinet space.
accuracy:detected terminal 0.1%:operated terminal:0.2%
power supply:20~30VDC
input signal:4~20mADC
output signal:4~20mADC
output resistance:detected terminal 500Ω;Operated terminal≤750Ω
safety parameter:
Voc(Vk)=28V  Isc(Ik)=93mA
Um=250Vrms/dc Ca=0.083 f  La=4.2mH
Explosion-proof grade:Ex(ia)Ⅱc 
Ambient temperature:5~40℃
RH:5%~85%
Working frequency:10~55Hz,amplitude ≤0.075mm
External magnetic field:≤400A/m
Without corrosive media which impact Nickel, chrome plating, non-ferrous metals and alloy in ambient.