Home> unit meter >> barrier >> HR-WP60476035-DL-EXA Current Input Isolated Barrier
  • Product number:MC-000467001360
  • Product name:Current Input Isolated Barrier
  • Product Type:HR-WP60476035-DL-EXA
  • Product nameplate:SAIC
  • Project Category:unit meter >> barrier >>
  • Manufacturer:Shanghai Automation Instrumentation Co., Ltd.
  • Sales unit: Shanghai Automation Instrumentation Marketing Center
  • Information download:Click to enter the download page  
  • Introduction
  • Specifications
The instrument can transmit the current signal from safety area to dangerous area through the isolated output of single-or dual independent current / voltage signal and distribute power for two-wire and three-wire transmitter. It also can be serial communicating connecting by the configure interface in safety area. It is the intelligent safety barrier products with online self-diagnostic function. Users can also set input signal and output range via a dedicated hand-held programmed device or computer.
Explosion-proof mark:Ex(ia)ⅡC 
Transfer Accuracy:±0.2%×F.S
allowable input signal in dangerous area:
DC current:0-10mA、4-20mA
input impedance:100Ω
power voltage:no-load<28V,full-load>22V
input signal to safety area:
DC current:0~10mA、4~20mA、0~20mA;DC voltage:0~5V,1~5V,0~10V
NEPSI certification parameter(between 9 and 10 terminal):
Uo=28V,Io=93mA,Co=0.083μF,Lo=4.2mH
apply range:DC current signal from transmitter, first instrument and second instrument.
communication(safety area):RS232 or RS485 interface
power supply:DC 24V±10%
power consumption:1.3W(single-loop 20mAoutput,24V power supply);2.4W(dual-loop 20mAoutput,24V power supply)
case size:22.5×100×115mm